DocumentCode
1824224
Title
Withstand voltage performance of outer-rib type suspension insulators subjected to ice accretion under DC voltage application
Author
Song, P. ; Wang, Q. ; Wang, Y.G. ; Ito, S. ; Sun, W. ; Kondo, K. ; Imakoma, T. ; Dong, G.
Author_Institution
Southwest Electr. Power Design Inst., State Power Corp. of China, Sichuan, China
Volume
3
fYear
2003
fDate
1-5 June 2003
Firstpage
1028
Abstract
Artificial icicle was built up on the outer-rib and DC-Fog type suspension insulator strings, and withstand voltage tests were carried out. In case of the outer-rib type insulator, some air gaps were found remaining among the accreted icicles and it takes more time for icicles to completely bridge between the insulators, comparing to DC-Fog type. Therefore, excellent withstand voltage performance of the outer-rib type suspension insulator was observed under ice accretion condition.
Keywords
air gaps; ice; insulator testing; suspensions; DC-Fog type suspension insulator strings; accreted icicles; air gaps; artificial icicle; ice accretion; outer-rib type suspension insulators; withstand voltage tests; Conductivity; Dielectrics and electrical insulation; Electrical resistance measurement; Ice surface; Insulator testing; Power transmission lines; Spraying; Sun; Surface resistance; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Properties and Applications of Dielectric Materials, 2003. Proceedings of the 7th International Conference on
ISSN
1081-7735
Print_ISBN
0-7803-7725-7
Type
conf
DOI
10.1109/ICPADM.2003.1218597
Filename
1218597
Link To Document