DocumentCode
1824759
Title
The statistical properties of PD distribution in oil-impregnated insulation at elevated temperature
Author
Ariastina, W.G. ; Khawaja, R.H. ; Blackburn, T.R.
Author_Institution
Sch. of Electr. Eng. & Telecommun., Univ. of New South Wales, Sydney, NSW, Australia
Volume
3
fYear
2003
fDate
1-5 June 2003
Firstpage
1116
Abstract
This paper presents a study of the properties of partial discharges at elevated temperature. Particular interest was given to new and aged oil-impregnated insulation as applied in power and instrument transformers. The data analysis was focused on the PD quantities that include the peak and average PD magnitudes and the PD repetition rate. In addition to the PD quantities, an investigation of the discharge characteristics using statistical moments was also conducted. Results indicated that the PD quantities and the characteristics of their distributions are greatly affected by the temperature change. Variation in the PD activity was found to be considerable and very dependent on the insulation condition.
Keywords
impregnated insulation; instrument transformers; partial discharge measurement; power transformer insulation; statistical analysis; transformer oil; instrument transformer; oil impregnated insulation; partial discharge distribution; power transformer; statistical moment; statistical properties; Aging; Dielectrics and electrical insulation; Heating; Oil insulation; Partial discharges; Petroleum; Power transformer insulation; Temperature distribution; Testing; Thermal stresses;
fLanguage
English
Publisher
ieee
Conference_Titel
Properties and Applications of Dielectric Materials, 2003. Proceedings of the 7th International Conference on
ISSN
1081-7735
Print_ISBN
0-7803-7725-7
Type
conf
DOI
10.1109/ICPADM.2003.1218619
Filename
1218619
Link To Document