DocumentCode :
1833803
Title :
Tracking MOV operability under degraded voltage condition by periodic test measurements
Author :
Hussain, B. ; Behera, A.K. ; Alsammarae, A.J.
Author_Institution :
KCI Eng. Consultants, Downers Grove, IL, USA
Volume :
2
fYear :
1996
fDate :
2-9 Nov 1996
Firstpage :
965
Abstract :
The purpose of this paper is to develop a methodology for evaluating the operability of Alternating Current (AC) Motor Operated Valve (MOV) under degraded voltage condition, based on the seating parameter measured during surveillance/testing. This approach will help resolve Nuclear Regulatory Commission´s (NRC´s) concern on verifying the AC MOV´s design basis capability through periodic testing
Keywords :
AC motor drives; AC motors; fission reactor cooling; fission reactor safety; machine testing; nuclear power stations; valves; AC motor operated valve; MOV operability; NPP safety; Nuclear Regulatory Commission; degraded voltage condition; design basis capability; nuclear reactor valves; periodic test measurements; seating parameter; AC motors; Current measurement; Degradation; Nuclear power generation; Surveillance; Switches; Testing; Torque; Valves; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Nuclear Science Symposium, 1996. Conference Record., 1996 IEEE
Conference_Location :
Anaheim, CA
ISSN :
1082-3654
Print_ISBN :
0-7803-3534-1
Type :
conf
DOI :
10.1109/NSSMIC.1996.591508
Filename :
591508
Link To Document :
بازگشت