• DocumentCode
    1844670
  • Title

    Impact of non-simultaneous P/f and Q/V grid code requirements on PV inverters on unintentional islanding operation in distribution network

  • Author

    Lissandron, Stefano ; Sgarbossa, Riccardo ; Dalla Santa, Luca ; Mattavelli, Paolo ; Turri, Roberto ; Cerretti, Alberto

  • Author_Institution
    Dept. of Inf. Eng., Univ. of Padova, Padua, Italy
  • fYear
    2015
  • fDate
    22-25 June 2015
  • Firstpage
    1
  • Lastpage
    7
  • Abstract
    The analysis of unintentional islanding in distribution grids with a large penetration of renewable energy sources is of increasing interest due to the recently introduced requirements of P/f and Q/V supporting capabilities of Distributed Energy Resources (DERs) and the wider frequency and voltage ranges, DERs should be able to operate with, before protection tripping. DER anti-islanding protections, if present, may fail to detect this grid transition and so uncontrolled islanding operation may appear. Since this operating mode may be dangerous for the electric network operation and may cause damages for the grid equipment, in this paper the increase of its risk due to P/f and Q/V droop characteristics of generators is addressed. Analytic results are initially derived for the steady-state unintentional islanding operation and then they are validated on a laboratory-scale grid setup. The proposed investigation will show that the risk of permanent unintentional islanding increases introducing P/f or Q/V droop regulation and that such risk is maximum including both the P/f and Q/V droop regulations, rather than only one of them.
  • Keywords
    distributed power generation; invertors; power apparatus; power distribution faults; power distribution reliability; power grids; renewable energy sources; solar cells; DER antiislanding protection; P-f droop regulation; PV inverter; Q-V droop regulation; distributed energy resource; distribution grid transition; distribution network; electric network operation; grid equipment; nonsimultaneous P-f grid code requirement; nonsimultaneous Q-V grid code requirement; protection tripping; renewable energy source; steady-state unintentional islanding operation; Density estimation robust algorithm; Inverters; Islanding; Reactive power; Steady-state; Threshold voltage; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Electronics for Distributed Generation Systems (PEDG), 2015 IEEE 6th International Symposium on
  • Conference_Location
    Aachen
  • Type

    conf

  • DOI
    10.1109/PEDG.2015.7223095
  • Filename
    7223095