• DocumentCode
    1846956
  • Title

    Reducing the impact of DG in distribution networks protection using fault current limiters

  • Author

    Agheli, Ali ; Abyaneh, Hossein Askarian ; Chabanloo, Reza Mohammadi ; Dezaki, Hamed Hashemi

  • Author_Institution
    Electr. Eng. Dept., Amirkabir Univ. of Technol., Tehran, Iran
  • fYear
    2010
  • fDate
    23-24 June 2010
  • Firstpage
    298
  • Lastpage
    303
  • Abstract
    The connecting of distributed generation (DG) to distribution network has numerous advantages. However, the presence of these sources leads distribution networks to lose their radial nature. Some problems in coordination of protection devices will occur, due to changes in short circuit levels in different points. In this paper, the effect of size and location of DGs on overcurrent relay coordination has been investigated. The use of fault current limiter (FCL) is proposed to limit fault current levels and effect of DGs on coordination of overcurrent relay during the fault. The procedure of selecting of FCL impedance type and its size is presented to restore the effective coordination of overcurrent relays. The efficiency of the proposed technique is demonstrated by comparing the results of a typical network with those obtained using the previous techniques.
  • Keywords
    fault current limiters; overcurrent protection; power distribution protection; distributed generation; distribution networks protection; fault current limiters; overcurrent relay coordination; Biological cells; Circuit faults; Fault currents; Impedance; Optimization; Power engineering; Relays; Distributed generation; distribution system protection; fault current limiter (FCL); overcurrent relay;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering and Optimization Conference (PEOCO), 2010 4th International
  • Conference_Location
    Shah Alam
  • Print_ISBN
    978-1-4244-7127-0
  • Type

    conf

  • DOI
    10.1109/PEOCO.2010.5559205
  • Filename
    5559205