Abstract :
On-site diagnosis methods for quality assessment of large power transformers rise in importance, as deregulation of the energy market demands an improved life time management for expensive equipment. Here, the three complementing methods in use in Switzerland are discussed: Off-line partial discharge diagnosis (PD), frequency response analysis (FRA) and polarisation/depolarisation current measurements (PDC). For PD and for FRA noteworthy experience exists already. However, the PDC method became only recently available as an user-friendly method; its aptitude is described in detail and it is shown how to obtain information on the integral condition of the oil-cellulose insulation system from PDC measurements
Keywords :
frequency response; insulation testing; partial discharge measurement; power transformer insulation; power transformer testing; transformer oil; frequency response analysis; off-line partial discharge diagnosis; oil-cellulose system; on-site diagnosis; polarisation/depolarisation current measurement; power transformer insulation; quality assessment; Current measurement; Energy management; Frequency response; Oil insulation; Partial discharges; Polarization; Power transformers; Quality assessment; Quality management; US Department of Transportation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2001 Annual Report. Conference on
Conference_Location :
Kitchener, Ont.
Print_ISBN :
0-7803-7053-8
Type :
conf
DOI :
10.1109/CEIDP.2001.963577
Filename :
963577
Link To Document :
بازگشت