Title :
SSIMS molecular selective imaging: A new diagnostic tool to investigate metal passivators in scrapped transformers
Author :
Facciotti, M. ; Amaro, P.S. ; Brown, R.C.D. ; Lewin, P.L. ; Pilgrim, J.A. ; Wilson, G. ; Jarman, P.N.
Author_Institution :
Univ. of Southampton, Southampton, UK
Abstract :
In every high voltage grid, the replacement of assets is a slow but steady process that guarantees long-term reliability of the power distribution networks. The prioritisation of such interventions is based on complex rating criteria specifically designed to highlight potential issues of certain machines (or families of machines) in need of care. Given the tremendous costs of operations such as the replacement of a power transformer it is not surprising to observe constant efforts devoted to finding new and better monitoring and diagnostic tools. These are capable of delivering invaluable information about the conditions of a transformer, in service or after it is either failed or proactively scrapped, allowing a better comprehension of underlying chemical-physical phenomena occurring. Ideally, advanced monitoring and diagnostic tools should ultimately result in improved rating parameters to be applied in the evaluation of future interventions. This feasibility study evaluates the use of static secondary ion mass spectrometry (SSIMS) molecular selective imaging as a diagnostic tool for power transformer. SSIMS is herein demonstrated to be able to assess, without doubts, the presence and integrity of the passivation layer produced by Irgamet®39 on copper surfaces in laboratory tests. The technique has also been tested on real samples collected from one of the phases of a 400/275kV autotransformer proactively scrapped and proved to be applicable without significant sample preparation. The possibility of its use in the study of the distribution of Irgamet®39 across the windings is also demonstrated. Further development of SSIMS as a diagnostic tool would be significantly increasing the grade of detail at which scrapped/failed units could be inspected. A better understanding on how the operating conditions or the design of a transformer can affect the anticorrosion protection layer at the molecular level would open the way to signi- icant ad hoc improvements of both operative guidelines and rating criteria for power transformers.
Keywords :
autotransformers; corrosion protective coatings; failure analysis; passivation; power transformer testing; secondary ion mass spectroscopy; Irgamet 39; SSIMS molecular selective imaging; anticorrosion protection layer; assets replacement; autotransformer; chemical-physical phenomena; complex rating criteria; copper surfaces; diagnostic tools; high voltage grid; monitoring tools; operating conditions; operative guidelines; passivation layer; power distribution networks; power transformer replacement; rating parameters; static secondary ion mass spectrometry molecular selective imaging; voltage 275 kV; voltage 400 kV; Copper; Oil insulation; Passivation; Power transformer insulation; Sulfur; Windings; SSIMS; corrosive sulphur; diagnostics; passivator; scrapping; transformer;
Conference_Titel :
Electrical Insulation Conference (EIC), 2015 IEEE
Conference_Location :
Seattle, WA
Print_ISBN :
978-1-4799-7352-1
DOI :
10.1109/ICACACT.2014.7223492