• DocumentCode
    1854902
  • Title

    Evolution of ac and impulse breakdown strength of HV XLPE cable after long term test. Correlation with physical properties

  • Author

    Bezille, J. ; Janah, H. ; Chan, J. ; Hartley, M.

  • Author_Institution
    Alcatel Cable, Calais, France
  • fYear
    1994
  • fDate
    23-26 Oct 1994
  • Firstpage
    582
  • Lastpage
    587
  • Abstract
    Despite the good knowledge of actual materials for HV insulation cable, the influence of aging on dielectric properties is not well known. Recent 90 kV XLPE cable aged on site with load cycles has been investigated just after fabrication, after 15 000 hours and 30 000 hours aging. In addition, the thermal loop after 30 000 hours only stressed with thermal cycles is also under investigation, allowing separation of thermal and electrical stresses influence on insulation aging. Electrical and physical properties are followed with aging time and compared with those of unaged insulation
  • Keywords
    ageing; 15000 hour; 30000 hour; 90 kV; AC breakdown strength; HV cable insulation; XLPE; aging; dielectric properties; electrical stress; impulse breakdown strength; long term test; thermal cycles; thermal loop; thermal stress; Aging; Dielectric breakdown; Dielectric materials; Dielectric thin films; Dielectrics and electrical insulation; Electric breakdown; Impulse testing; Performance evaluation; Thermal stresses; Wire;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 1994., IEEE 1994 Annual Report., Conference on
  • Conference_Location
    Arlington, TX
  • Print_ISBN
    0-7803-1950-8
  • Type

    conf

  • DOI
    10.1109/CEIDP.1994.592033
  • Filename
    592033