DocumentCode
1855217
Title
Fault development on water ingress in damaged underground Low Voltage cables with plastic insulation
Author
Kruizinga, B. ; Wouters, P.A.A.F. ; Steennis, E.F.
Author_Institution
Electr. Energy Syst. group, Eindhoven Univ. of Technol., Eindhoven, Netherlands
fYear
2015
fDate
7-10 June 2015
Firstpage
309
Lastpage
312
Abstract
Increased pressure on condition monitoring of Low Voltage (LV) underground power cables can be expected due to rising penetration of de-central generation. Digging damage plays a large role in LV cable failure statistics while those damages do not necessarily lead to an outage directly. Artificially damaged cable sections of two commonly used LV cable types have been tested on water exposure. Upon water evaporation, partial discharges occur causing degradation of the insulation material. In one case this was found to lead to breakdown. Several dependencies can be identified that need further investigation. These results enhances the understanding of failure behavior as it may take place underground for cables in service, and can be used in the development of condition monitoring techniques and lifetime predictions.
Keywords
condition monitoring; failure analysis; partial discharges; power cable insulation; power system faults; underground cables; cable failure statistics; condition monitoring techniques; decentral generation; fault development; insulation material; partial discharges; plastic insulation; underground low voltage cables; underground power cables; water ingress; Cable insulation; Conductors; Electric breakdown; Electromagnetic compatibility; Q measurement; Reliability; asset management; plastic insulation; power cable insulation; power distribution;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation Conference (EIC), 2015 IEEE
Conference_Location
Seattle, WA
Print_ISBN
978-1-4799-7352-1
Type
conf
DOI
10.1109/ICACACT.2014.7223568
Filename
7223568
Link To Document