• DocumentCode
    1865506
  • Title

    First year performance of a 20 MWac PV power plant

  • Author

    Panchula, Alex F. ; Hayes, William ; Bilash, John ; Kimber, Adrianne ; Graham, Cindy

  • Author_Institution
    First Solar, Oakland, CA, USA
  • fYear
    2011
  • fDate
    19-24 June 2011
  • Abstract
    Summary form only given. After one year of continuous operation in Ontario, Canada, the actual performance of the Sarnia 20MWac power plant can be compared to both the long-term energy prediction and the expected energy for the operating year 2010. The long-term prediction uses satellite meteorological data and loss assumptions and the PVSYST system simulation tool to estimate the behavior of the power plant over a "typical" year. Typical meteorological input from satellite data is discretized on a monthly basis; therefore the monthly Performance Ratio (PR) is an appropriate metric for comparison. Our comparison shows that the prediction data is in line with the actual power plant PR during normal operation. However, energy lost due to snowfall remains one major prediction difficulty. Based on the first year\´s data at the Enbridge\´s Sarnia 20 MWac power plant, the power plant is operating within 2.1% of the long-term prediction. Using the one year of on-site meteorological data, the expected energy of the site for 2010 can be found by rerunning the prediction with hourly measured data. At this time-step, specific measurement points within the power plant can be assessed by simply comparing measured to expected values, including the DC and AC energy at the inverters as well as the module temperature and inverter efficiency. The estimation of the modeling error at each of these measurement points shows that there is no single driver of the overall modeling error during normal operation, but also shows that improvements are possible. Actual energy from the Sarnia 20 MWac power plant was 0.6% more than expected based on the expected energy for the 2010 operating year.
  • Keywords
    invertors; load forecasting; photovoltaic power systems; AC energy; Canada; DC energy; Enbridge Sarnia power plant; Ontario; PV power plant; PVSYST system simulation tool; energy lost; expected energy; inverter efficiency; long-term energy prediction; loss assumptions; modeling error estimation; module temperature; performance ratio; power 20 MW; satellite meteorological data; Energy measurement; IEEE Xplore; Inverters; Power generation; Power measurement; Satellites; Temperature measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Photovoltaic Specialists Conference (PVSC), 2011 37th IEEE
  • Conference_Location
    Seattle, WA
  • ISSN
    0160-8371
  • Print_ISBN
    978-1-4244-9966-3
  • Type

    conf

  • DOI
    10.1109/PVSC.2011.6186344
  • Filename
    6186344