DocumentCode :
186941
Title :
Effects of stray capacitances on high voltage current transformers
Author :
Aristoy, Gonzalo ; Santos, Aldri ; Slomovitz, Daniel
Author_Institution :
Lab., UTE, Montevideo, Uruguay
fYear :
2014
fDate :
12-15 May 2014
Firstpage :
348
Lastpage :
351
Abstract :
This paper evaluates the effect of stray capacitances between primary and secondary windings on current transformers (CT) used in high voltage networks. Ground potential at all windings is the typical configuration during laboratory calibration. However, in service, the primary winding is at high voltage potential. The variation of current errors between both working conditions is evaluated for a set of CTs. A calibration system was developed that measures the transformer errors under nominal voltage operation, and experimental results on different type of transformers are presented.
Keywords :
calibration; capacitance measurement; current transformers; distribution networks; transformer windings; transmission networks; calibration system; current errors; high voltage current transformers; high voltage networks; stray capacitances; transformers windings; Bridge circuits; Current measurement; Electric potential; RNA; current transformer; high voltage; instrument transformer; isolation; parasitic capacitance; test;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Instrumentation and Measurement Technology Conference (I2MTC) Proceedings, 2014 IEEE International
Conference_Location :
Montevideo
Type :
conf
DOI :
10.1109/I2MTC.2014.6860765
Filename :
6860765
Link To Document :
بازگشت