• DocumentCode
    1870968
  • Title

    Consideration of controllability and observability of generators in the coherency-based dynamic equivalencing

  • Author

    Kasztel, Z. ; Erlich, I.

  • Author_Institution
    Dept. of Electr. Power Syst., Duisburg Univ., Germany
  • Volume
    2
  • fYear
    2001
  • fDate
    2001
  • Abstract
    This paper describes an improved method for developing dynamic equivalents. The method bases on the coherency of generators quantified by the correlation coefficient of the swing curves. For measuring the electromechanical distance of generators from the interesting areas, controllability and observability indices are defined. These are calculated on the base of the linearized system equations. A modified correlation formula is used for considering the controllability and observability. As a result, distance generators will be put together into a coherent group rather then those with large controllability and observability factors
  • Keywords
    controllability; machine control; observability; power system control; power system interconnection; power system stability; synchronous generators; coherency-based dynamic equivalencing; controllability indices; distance generators; dynamic equivalents; electromechanical distance; large interconnected power systems; linearized system equations; model aggregation; modified correlation formula; observability indices; power system stability; swing curves correlation coefficient; synchronous generators; Controllability; Equations; Load flow; Observability; Power generation; Power system dynamics; Power system interconnection; Power system modeling; Power system simulation; Power system stability;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Tech Proceedings, 2001 IEEE Porto
  • Conference_Location
    Porto
  • Print_ISBN
    0-7803-7139-9
  • Type

    conf

  • DOI
    10.1109/PTC.2001.964719
  • Filename
    964719