Title :
Emergency tap-blocking to prevent voltage collapse
Author :
Vournas, Costas D. ; Manos, George A.
Author_Institution :
Dept. of Electr. & Comput. Eng., Nat. Tech. Univ. of Athens, Greece
Abstract :
This paper proposes a technique for the selection of tap changers to be blocked as an emergency measure, in the case of long-term voltage instability. The instability is identified using a long-term sensitivity index and the tap changers to be blocked are selected based on the column sum of a voltage sensitivity matrix. This method is applied to a severe contingency in the heavily loaded Hellenic Interconnected Power System and it is shown to be able to mitigate the voltage degradation in the event of a long-term instability, so that an imminent voltage collapse is prevented
Keywords :
matrix algebra; power system control; power system dynamic stability; power system interconnection; power transformers; sensitivity analysis; emergency control; emergency tap-blocking; heavily loaded Hellenic Interconnected Power System; imminent voltage collapse; load tap changers; long-term sensitivity index; long-term voltage instability; severe contingency; tap changers selection; voltage collapse prevention; voltage degradation mitigation; voltage sensitivity matrix; Degradation; Power system interconnection; Power system measurements; Power system planning; Power system security; Power system stability; Substations; Transformers; Transmission line matrix methods; Voltage control;
Conference_Titel :
Power Tech Proceedings, 2001 IEEE Porto
Conference_Location :
Porto
Print_ISBN :
0-7803-7139-9
DOI :
10.1109/PTC.2001.964741