Comparison of time-domain methods for two-end PD location in power cables
Author :
Firdaus, A.F. ; Mardiana, R. ; Muyeen, S.M.
Author_Institution :
Electr. Eng. Dept., Pet. Inst., Abu Dhabi, United Arab Emirates
fYear :
2012
fDate :
April 29 2012-May 2 2012
Firstpage :
1
Lastpage :
6
Abstract :
Accuracy comparison of various time domain methods for locating of partial discharge (PD) in power cables is presented in this paper. The PD location is based on the measurement from two-end of the cable. The defect in the cable is located from the arrival time interval between the initial waves of a PD pulse. To estimate the time-of arrival, various methods such as peak detection, 50% pulse peak detection, threshold detection, Akaike Information Criterion, Energy Criterion, Gabor Centroid, and cross correlation are considered. The computer simulation has been carried out using a 20 kV, 1000-m underground cable. After comparison, it is found that peak detection has better performance than other methods.
Keywords :
partial discharge measurement; power cable insulation; time-domain analysis; time-of-arrival estimation; underground cables; PD location; PD pulse; arrival time interval; partial discharge measurement; power cable; size 1000 m; time-domain method; time-of-arrival estimation; underground cable; voltage 20 kV; Cable insulation; Cable shielding; Equations; Partial discharges; Power cables; Pulse measurements; Time domain analysis; PD location; cable insulation; partial discharge; time-of-arrival;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical & Computer Engineering (CCECE), 2012 25th IEEE Canadian Conference on
Conference_Location :
Montreal, QC
ISSN :
0840-7789
Print_ISBN :
978-1-4673-1431-2
Electronic_ISBN :
0840-7789
Type :
conf
DOI :
10.1109/CCECE.2012.6335064
Filename :
6335064
Link To Document :
بازگشت