• DocumentCode
    1873876
  • Title

    Study of the dynamic behavior of the Greek mainland system after the opening of the Greece-Bulgaria interconnection

  • Author

    Georgiadis, D.P. ; Hatziargyriou, N.D. ; Fourlaris, D. ; Blanas, I. ; Trastas, Th

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Nat. Tech. Univ. of Athens, Greece
  • Volume
    4
  • fYear
    2001
  • fDate
    2001
  • Abstract
    This paper presents studies carried out on the Hellenic system in order to assess the effect of the existence of only one main interconnection with the rest Balkan system, the Bulgaria interconnection. The dynamic behavior is analyzed for selected disturbances and shows that for large generation loss in the Greek network there is isolation of the Greek system, due to the short activation time of the Bulgaria overload protective device. In this case load shedding is necessary for safety reasons. In general it is concluded that the Greek system remains stable, even in large disturbances
  • Keywords
    control system analysis computing; load shedding; power system analysis computing; power system control; power system dynamic stability; power system faults; power system interconnection; Greece-Bulgaria power system interconnection; activation time; disturbances; dynamic behavior; generation loss; load shedding; overload protection; overload protective device; safety reasons; Adders; Control systems; Integrated circuit interconnections; Power system interconnection; Power system modeling; Protection; Safety; Springs; Stability; State estimation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Tech Proceedings, 2001 IEEE Porto
  • Conference_Location
    Porto
  • Print_ISBN
    0-7803-7139-9
  • Type

    conf

  • DOI
    10.1109/PTC.2001.964823
  • Filename
    964823