Sensitivity improvement of the digital differential relay for internal ground fault protection in the power transformer with tap changer
Author
Ahmed, Ahmed Y. ; Al-Mously, S.I.
Author_Institution
Dept. of Control Eng., Higher Inst. of Electron., Beni-Walid, Libya
Volume
4
fYear
2001
fDate
2001
Abstract
A new method for improving the sensitivity of the digital differential relays that used to detect the internal ground fault in the (Δ-Y) power transformer with on-load tap changer is presented in this paper. The suggested method can be applied to the digital relays and/or may be applied to the conventional differential relays. Digital differential relay is sensitive to internal faults, except the ground fault, due to the high current ratio required for transformer with tap changer. This is true especially for percentage differential relay. The adopted method deals with this case to increase the number of protected winding against ground faults from 35% to about 100%
Keywords
electrical faults; power transformer protection; relay protection; sensitivity analysis; digital differential relay; high current ratio; internal ground fault detection; internal ground fault protection; power transformer; sensitivity improvement; tap changer; Control engineering; Current transformers; Digital relays; Fault detection; Monitoring; On load tap changers; Power transformers; Protection; Protective relaying; Radar;