Title :
Harmonics and PQ events monitoring in an electrified metro-transit system
Author :
Capasso, A. ; Lamedica, R. ; Sangiovanni, S. ; Maranzano, G. ; Prudenzi, A.
Author_Institution :
Electr. Eng. Dept., La Sapienza Univ., Rome, Italy
Abstract :
The paper illustrates some results of a wide power quality (PQ) survey performed on the power supply installations of the metro-transit system serving the city of Rome, in Italy. The system currently includes two railway lines supplied at 1,500 V DC through several AC/DC 3.7 MW rated converters. The power supply of the system is provided at medium voltage (20 kV) from five different connections to the public grid. Fourteen electrical substations provide the total demand of about 20 MW of the system. The survey, currently still in progress, involves monitoring activities aimed at identifying possible PQ problems of various nature. Identification of typical daily patterns of harmonics distortion due to the system is even a task of the current survey.
Keywords :
AC-DC power convertors; harmonic distortion; light rail systems; monitoring; power supply quality; power system harmonics; substations; traction power supplies; 1500 V; 20 kV; 3.7 MW; AC/DC converters; Italy; PQ events monitoring; Rome; current survey; electrical substations; electrified metro-transit system; harmonic distortion; power quality; power supply installations; public grid; railway lines; Electronic switching systems; Monitoring; Postal services; Power supplies; Power system harmonics; Radio access networks; Sections; Senior members; Transformers; Voltage;
Conference_Titel :
Harmonics and Quality of Power, 2002. 10th International Conference on
Print_ISBN :
0-7803-7671-4
DOI :
10.1109/ICHQP.2002.1221475