Title :
Equipment sensitivity to voltage sags-test results for contactors, PCs and gas discharge lamps
Author :
Pohjanheimo, P. ; Lehtonen, M.
Author_Institution :
Power Syst. Lab., Helsinki Univ. of Technol., Espoo, Finland
Abstract :
Voltage sag tolerance levels were measured for samples of three equipment categories sensitive to sags: contactors, PCs and gas discharge lamps. An up-to-date voltage waveform generator was used to produce and repeat the events as necessary. Remaining voltage and sag duration were the test variables. For contactors also the effect of point-on-wave of sag initiation was studied. The results were rather well convergent with earlier studies by other institutes. This justifies more generalized conclusions on performance of these device categories as well as more statistical approach to the issue. This kind of typical equipment sensitivity data is needed as a library for the future sag assessment methods.
Keywords :
contactors; electric potential; equipment evaluation; industrial power systems; metal vapour lamps; microcomputers; power supply quality; statistical testing; tolerance analysis; waveform generators; PC; contactors; equipment sensitivity data; gas discharge lamp; industrial power system testing; personal computer; point-on-wave effect; power quality; sag assessment method; sag duration; statistical approach; voltage sag tolerance level; voltage sags-test result; voltage waveform generator; Contactors; Discharges; Lamps; Libraries; Personal communication networks; Power quality; Power system analysis computing; Power systems; System testing; Voltage fluctuations;
Conference_Titel :
Harmonics and Quality of Power, 2002. 10th International Conference on
Print_ISBN :
0-7803-7671-4
DOI :
10.1109/ICHQP.2002.1221496