• DocumentCode
    1877916
  • Title

    Partial discharges under moderately distorted voltage: a preliminary study

  • Author

    Emanuel, Alexander E.

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Worcester Polytech. Inst., MA, USA
  • Volume
    2
  • fYear
    2002
  • fDate
    6-9 Oct. 2002
  • Firstpage
    788
  • Abstract
    This study compares the number of partial discharges (PDs) per cycle NNS, caused by a nonsinusoidal voltage, with the number of partial discharges per cycle NS caused by a sinusoidal voltage with the same rms value as the sinusoidal one. The results are based on two theoretical models that account for peak, inception and residual voltages, a time-constant characteristic to the cavity´s geometry and deterioration as well as the voltage waveform. The obtained results indicate that for practical situations at power system busses with randomly varying harmonics, where the voltage distortion is low, THD≤5%, the expected partial discharge ratio is in the range 1 < NNS / NS ≤1 .05.
  • Keywords
    capacitance; dielectric materials; harmonic distortion; insulating materials; partial discharges; power system harmonics; PD; THD; cavitys geometry; deterioration; inception voltage; moderately distorted voltage; nonsinusoidal voltage; partial discharge ratio; peak voltage; power system busses; randomly varying harmonics; residual voltage; rms value; sinusoidal voltage; theoretical model; time-constant characteristic; voltage distortion; voltage waveform; Aging; Capacitance; Dielectric materials; Dielectrics and electrical insulation; Partial discharges; Power system harmonics; Power system modeling; Stress; Temperature; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Harmonics and Quality of Power, 2002. 10th International Conference on
  • Print_ISBN
    0-7803-7671-4
  • Type

    conf

  • DOI
    10.1109/ICHQP.2002.1221535
  • Filename
    1221535