Title :
Analysis and design modifications for upgrade of storage ring bump pulse system driving the injection bump magnets at the ALS
Author_Institution :
California Univ., Berkeley, CA, USA
Abstract :
A fast (4.0 ms half period) resonant discharge pulse system, using SCRs, was designed and constructed to drive the injection bump magnet system at the Advanced Light Source (ALS). The commissioning process revealed a high frequency resonance (T=800 NS) superimposed on the driver discharge wave form. In addition, the peak amplitude of the magnet load recovery current exceeded design specifications. A SPICE analysis confirmed the suspected mechanisms for the parasitic ringing and the excessive load current “undershoot”. This paper will address the subsequent analysis, measurements, and modifications carried out during the maintenance shutdown in June 1993
Keywords :
accelerator magnets; electron accelerators; particle beam injection; storage rings; ALS; Advanced Light Source; SPICE analysis; commissioning; driver discharge wave form; excessive load current; high frequency resonance; injection bump magnet system; injection bump magnets; magnet load recovery current; maintenance shutdown; parasitic ringing; storage ring bump pulse system; Circuits; Magnetic analysis; Magnetic switching; Magnets; Pulse measurements; Resonance; SPICE; Storage rings; Switches; Thyristors;