    Digital simulation of fault transients on six-phase transmission systems

  • Author

    Song, Y.H. ; Johns, A.T. ; Aggarwal, R.K.

  • Author_Institution
    Bath Univ., UK
  • fYear
    1993
  • fDate
    7-10 Dec 1993
  • Firstpage
    385
  • Abstract
    High phase order transmission, i.e. more than three-phase, is a unique approach to increasing the power transmission capability of overhead electric power transmission over existing rights-of-way. The introduction of this new technology, however, causes some line protection problems. This paper presents studies relating to the fault arcing transients on a six-phase system with particular reference to the development of adaptive autoreclosure. The arc modelling techniques previously developed by the authors are employed. Comprehensive digital simulation is then presented on a 326 kV six-phase system under various system and fault conditions. The implications of the results on the development of adaptive autoreclosure scheme are also briefly discussed
  • Keywords
    arcs (electric); digital simulation; electrical faults; power overhead lines; power system analysis computing; power system protection; power system transients; transmission networks; 326 kV; adaptive autoreclosure; arc modelling; development; digital simulation; fault arcing transients; overhead electric power transmission; power transmission capability; protection; six-phase; transmission systems;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Advances in Power System Control, Operation and Management, 1993. APSCOM-93., 2nd International Conference on
  • Conference_Location
    IET
  • Print_ISBN
    0-85296-569-9
  • Type

    conf

  • Filename
    292743