• DocumentCode
    1884602
  • Title

    Loop heat pipe technology for cooling computer servers

  • Author

    Zimbeck, Walter ; Slavik, Greg ; Cennamo, John ; Kang, Sukhvinder ; Yun, James ; Kroliczek, Edward

  • Author_Institution
    Technol. Assessment & Transfer, Inc., Annapolis, MD
  • fYear
    2008
  • fDate
    28-31 May 2008
  • Firstpage
    19
  • Lastpage
    25
  • Abstract
    An air cooled loop heat pipe (LHP) system was developed for cooling a dual CPU 1U server. The LHP uses newly developed flat plate evaporators and air cooled condensers with millimeter scale condensation channels and plain parallel fins. Bench tests were conducted using 20 x 20 mm uniform heat sources dissipating 100 watts and air preheating to simulate air-cooled operation within a 1U server chassis. Thermal resistance was decreased as the air temperature increased from 25degC to 50degC. At 50degC air temperature, the LHP evaporator surface temperature reached 65degC showing an effective evaporator surface to air thermal resistance of 0.15degC/W. A commercial 1U server with dual 100 W rated Intel Xeon processors was used to compare the effectiveness of the LHP cooling system to the standard processor fan heat sinks. Multiple instances of CPU Burn were used to exercise the CPU´s for maximum power dissipation. Under similar test conditions with room air temperature in the range 26-30degC, the interface temperature at the processors stabilized at ~75degC with the fan heat sinks and ~55degC with the LHP cooling system.
  • Keywords
    cooling; heat pipes; microprocessor chips; thermal resistance; air cooled loop heat pipe system; cooling computer servers; dual CPU 1U server; flat plate evaporators; loop heat pipe technology; millimeter scale condensation channels; thermal resistance; Central Processing Unit; Cooling; Heat pumps; Heat sinks; Heat transfer; Military computing; Resistance heating; Space heating; Thermal resistance; Water heating; 1U server; Xeon processors; compact condenser; electronics cooling; flat plate evaporator; loop heat pipe; military electronics; two phase cooling;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Thermal and Thermomechanical Phenomena in Electronic Systems, 2008. ITHERM 2008. 11th Intersociety Conference on
  • Conference_Location
    Orlando, FL
  • ISSN
    1087-9870
  • Print_ISBN
    978-1-4244-1700-1
  • Electronic_ISBN
    1087-9870
  • Type

    conf

  • DOI
    10.1109/ITHERM.2008.4544248
  • Filename
    4544248