• DocumentCode
    1886285
  • Title

    Cable management arm airflow impedance study

  • Author

    Rubenstein, Brandon

  • Author_Institution
    Hewlett Packard Co., Fort Collins, CO
  • fYear
    2008
  • fDate
    28-31 May 2008
  • Firstpage
    577
  • Lastpage
    582
  • Abstract
    A heavily loaded cable management arm at the rear of a server system can have the visual appearance of presenting a significant obstruction to airflow. Tests were carried out to evaluate the level of airflow impedance presented by a fully cabled arm in a relatively low profile server system. This investigation reveals that airflow pressure drop due to the presence of the cable management arm is less than 2% of the overall system impedance at typical operating conditions. This level of impedance would cause a nearly imperceptible temperature rise within the system.
  • Keywords
    cables (electric); data communication equipment; electric impedance; network servers; cable management arm airflow impedance; heavily loaded cable management arm; low profile server system; Arm; Communication cables; Cooling; Energy management; Impedance; Performance evaluation; Power system management; Power system reliability; System testing; Temperature; CMA; arm; cable; flow; impedance; management; pressure;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Thermal and Thermomechanical Phenomena in Electronic Systems, 2008. ITHERM 2008. 11th Intersociety Conference on
  • Conference_Location
    Orlando, FL
  • ISSN
    1087-9870
  • Print_ISBN
    978-1-4244-1700-1
  • Electronic_ISBN
    1087-9870
  • Type

    conf

  • DOI
    10.1109/ITHERM.2008.4544320
  • Filename
    4544320