Title :
Influence on harmonic emission limits of coincidence factor of electrified railway load
Author :
Xie, Shaofeng ; Li, Qunzhan ; Zhao, Liping
Author_Institution :
Coll. of Electr. Eng., Southwest Jiaotong Univ., China
Abstract :
This paper studies how to apply the coincidence factors proposed by IEC61000-3-6 to electrified railway load. It is proved that the coincidence factors of traction loads are more and more stable with number of traction substation increasing based on statistic and calculation of a lot of measurement data of electrified railway. Factual coincidence factors of traction loads are put forward and the influence of coincidence factors on distribution of harmonic emission limits to users is illustrated in this paper. When individual user´s harmonic emission level is evaluated, sufficient consideration of coincidence factors is necessary especially for peculiar user, such as electrified railway. It makes power quality standard involved in harmonic more rational.
Keywords :
power supply quality; railway electrification; traction; IEC61000-3-6; electrified railway load coincidence factor; harmonic emission limits; power quality standard; traction loads; traction substation; Cogeneration; Educational institutions; Harmonic distortion; Power quality; Power system harmonics; Rail transportation; Railway electrification; Statistical distributions; Substations; Voltage;
Conference_Titel :
Power Electronics Specialists Conference, 2004. PESC 04. 2004 IEEE 35th Annual
Print_ISBN :
0-7803-8399-0
DOI :
10.1109/PESC.2004.1355554