Title :
Effect of temperature on sensitivity of diagnostic tests on oil-impregnated paper insulation
Author :
Densley, R.J. ; Gupta, B.K.
Author_Institution :
ArborLec Solutions, Mississauga, Ont., Canada
Abstract :
In today´s economic climate, it is important for utilities to know the condition, by means of suitable diagnostic tests, of the oil impregnated paper used as the primary insulation in equipment such as transformers, switchgear, bushings, cables and their accessories. The results of several diagnostic tests on aged and unaged bushings are described in this paper. The test techniques include tan delta and loss current waveforms at 60 Hz, dielectric spectroscopy from 0.1 to 100 Hz, and recovery voltage. The results show that some of the techniques were able to detect significant changes in aged bushings, particularly at high temperatures. Further work is, however, recommended to improve our understanding of the changes in parameters such as loss current waveform, low frequency tan delta, and recovery voltage
Keywords :
bushings; capacitance measurement; dielectric loss measurement; impregnated insulation; insulating oils; insulation testing; voltage measurement; 0.1 to 100 Hz; accessories; aged bushings; bushings; cables; capacitance measurements; diagnostic tests temperature sensitivity; dielectric spectroscopy; loss current waveforms measurement; oil impregnated paper insulation; recovery voltage measurement; switchgear; tan delta measurement; transformers; unaged bushings; Aging; Cable insulation; Dielectric losses; Dielectrics and electrical insulation; Insulation testing; Insulators; Oil insulation; Petroleum; Power transformer insulation; Temperature sensors;
Conference_Titel :
Electrical Insulation Conference and Electrical Manufacturing & Coil Winding Conference, 2001. Proceedings
Conference_Location :
Cincinnati, OH
Print_ISBN :
0-7803-7180-1
DOI :
10.1109/EEIC.2001.965765