  • Abstract
    We detect the location of line outages inside a specific area of the power system from synchrophasor measurements at the border of the area and inside the area. We process the area synchrophasor measurements using a DC load flow model of the area. The processed measurements do not respond to line trips or power redispatches outside the area. The method extends previous methods that locate line trips in an entire network so that they work in a particular area and also deals with cases of islanding. The method will be particularly useful when utilities or ISOs in large interconnections restrict their attention to network models and phasor measurements for only their own area.
  • Keywords
    ISO standards; fault diagnosis; load flow; phasor measurement; DC load flow model; ISO; area synchrophasor measurements; islanding; line outages location; network models; power system; Area measurement; Generators; Load modeling; Power measurement; Power systems; Transmission line measurements; Vectors; Phasor measurement; event detection; power system monitoring; power transmission; smart grid; synchrophasor;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    North American Power Symposium (NAPS), 2012
  • Conference_Location
    Champaign, IL
  • Print_ISBN
    978-1-4673-2306-2
  • Electronic_ISBN
    978-1-4673-2307-9
  • Type

    conf

  • DOI
    10.1109/NAPS.2012.6336315
  • Filename
    6336315