Abstract :
This paper introduces a planning tool developed for estimating the maximum time-varying (dynamic) load that a substation distribution transformers can tolerate without violating hottest-spot (HST) and top-oil temperature (TOT) thermal limits. Presented are two kinds of HST and TOT models: the traditional ANSI Clause 7 models and linearized thermal models with coefficients optimized through linear regression to reveal the relationship between HST, TOT, ambient temperature and load. These models, along with Newton´s method, are shown to be capable of performing dynamic loading calculations.
Keywords :
Newton method; regression analysis; transformer substations; ANSI Clause 7 models; HST model; Newton method; TOT thermal limit model; dynamic loading calculations; linear regression; linearized thermal models; maximum time-varying load estimation; planning tool; production grade environment; substation distribution transformers; top-oil temperature thermal limits; violating hottest-spot; Cooling; Data models; Load modeling; Loading; Mathematical model; Oil insulation; Temperature measurement;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
North American Power Symposium (NAPS), 2012
Conference_Location :
Champaign, IL
Print_ISBN :
978-1-4673-2306-2
Electronic_ISBN :
978-1-4673-2307-9
Type :
conf
DOI :
10.1109/NAPS.2012.6336380
Filename :
6336380
Link To Document :
بازگشت