DocumentCode
190210
Title
SSR alleviation by STATCOM in induction generator based wind farm connected to series compensated line
Author
Moharana, Akshaya ; Varma, Rajiv ; Seethapathy, Ravi
Author_Institution
Electrical and Computer Engineering Dept., University of Western Ontario
fYear
2014
fDate
14-17 April 2014
Firstpage
1
Lastpage
1
Abstract
In this paper, a STATCOM with voltage controller is proposed to mitigate the potential of SSR in a series compensated IG based wind farm. Detailed eigenvalue analysis is performed to demonstrate that Induction Generator effect SSR is successfully alleviated by STATCOM. The results are validated through electromagnetic transient simulation with PSCAD/EMTDC. The impacts of symmetrical fault at different locations and collector cables are investigated and the effectiveness of the proposed STATCOM controller is illustrated. It is shown that a three phase fault close to the wind farm may cause severe oscillations in the PCC voltage, electromagnetic torque and shaft torque of the wind turbine generator. To examine this situation, an equivalent circuit analysis is presented, which predicts the threshold resonant speeds within which the wind turbine becomes unstable. The study is extended to other commercially available induction generators, which also shows the potential for SSR even at realistic levels of series compensation levels, and the capability of the proposed STATCOM controller to obviate its occurrence.
fLanguage
English
Publisher
ieee
Conference_Titel
T&D Conference and Exposition, 2014 IEEE PES
Conference_Location
Chicago, IL, USA
Type
conf
DOI
10.1109/TDC.2014.6863168
Filename
6863168
Link To Document