  • Abstract
    A make before break asymmetrical tap changer for a 10 kVA three phase two core phase shifting transformer with tap changing capability was created for lab use. The tap changer limits circulating current to below 15 A when changing tap positions, has a minimum contact force of 4 psi while changing taps in 0.5 seconds, and has a 10 degree phase shift in one degree increments. The transformer consists of two cores; an excitation core and a series core and will be used as a teaching tool and research instrument in a model power system lab.
  • Keywords
    on load tap changers; power engineering education; apparent power 10 kVA; asymmetrical phase shifting transformer; asymmetrical tap changer; changing taps; circulating current; contact force; excitation core; model power system lab; research instrument; series core; teaching tool; three-phase two-core phase shifting transformer; time 5 s; Bridge circuits; Brushes; Copper; Power transformer insulation; Resistors; Wires;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    North American Power Symposium (NAPS), 2012
  • Conference_Location
    Champaign, IL
  • Print_ISBN
    978-1-4673-2306-2
  • Electronic_ISBN
    978-1-4673-2307-9
  • Type

    conf

  • DOI
    10.1109/NAPS.2012.6336438
  • Filename
    6336438