Experience in material selection for grounding systems for power transmission towers
Author :
Abreu, Antonio
Author_Institution :
Chief of the Engineering Maintenance Transmission CORPOELEC the National Electricity Corporation
fYear :
2014
fDate :
14-17 April 2014
Firstpage :
1
Lastpage :
5
Abstract :
It is very common in technical design of transmission lines errors in the selection of materials to be used for grounding systems and do not take into account the type of soil and the material bases of the towers. This error can cause accelerated corrosion problems as which to go meet degrading and resistance values defined grounding for the design of the line, will cause increased likelihood of Back Flashover phenomena causing increased forced outputs actual lightning, to the point that exceeds the design, degrading the quality of service. This research presents a case study of electric transmission line towers have concrete bases type "pillar" cylindrical where a poor selection of the material for the equity this accelerated corrosion filed within twenty (21) months after construction. Based on this research, experience and literature proposes a number of technical criteria which should be taken into account when choosing the materials for the grounding system of power transmission line in order to minimize corrosion problems and theft.
Keywords :
Concrete Base; Counterpoise; Galvanic Corrosion; Galvanized Steel Base; Grounding System; Methodology; Theft; Transmission Tower; Ufer Grounding;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
T&D Conference and Exposition, 2014 IEEE PES
Conference_Location :
Chicago, IL, USA
Type :
conf
DOI :
10.1109/TDC.2014.6863318
Filename :
6863318
Link To Document :
بازگشت