  • Abstract
    This paper presents an experimental study on the tuning of an industrial fuzzy logic controller (FLC) for a shell-and-tube heat exchanger system. The objective of the experiment is to study the effect of FLC´s scaling factors (e, Δe Δu) to temperature controllability of the heat-exchanger system. Various values for e, Δe and Δu were set to FLC, and the process response (temperature) was observed. The result showed that a smaller value of e resulted in process instability, while a larger value would led to slower process response. Contrary to e, a smaller value of Δe resulted in slower process response, while a larger value would led to process instability. For Δu, a smaller value resulted in slower process response, while a larger value led to process instability.
  • Keywords
    fuzzy control; heat exchangers; process control; stability; temperature control; controller tuning; industrial fuzzy logic controller; process response; scaling factor effect; shell-and-tube heat exchanger system; temperature controllability; Fuzzy logic; Process control; Separation processes; Temperature; Tuning; Water heating;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Control and System Graduate Research Colloquium (ICSGRC). 2010 IEEE
  • Conference_Location
    Shah Alam
  • Print_ISBN
    978-1-4244-7238-3
  • Type

    conf

  • DOI
    10.1109/ICSGRC.2010.5562518
  • Filename
    5562518