DocumentCode
1911997
Title
An enhanced method of providing sensitive bus fault protection
Author
Stringer, Norman T.
Author_Institution
Artwel Electric, Inc, Sacramento, CA, USA
fYear
2001
fDate
37012
Firstpage
127
Lastpage
132
Abstract
The application of bus fault protection in industrial facilities has been primarily limited to overcurrent relays located at the upstream breaker. This does not always provide the best protection for bus faults. The protection sensitivity is limited because of the need to coordinate with other downstream overcurrent devices. This paper describes an enhanced method of applying sensitive bus fault protection using digital overcurrent relays. In addition, this method provides both downstream feeder breaker backup protection and relay backup protection
Keywords
industrial power systems; overcurrent protection; power distribution faults; power distribution protection; relay protection; bus fault protection; digital overcurrent relays; downstream feeder breaker backup protection; downstream overcurrent devices coordination; industrial facilities; overcurrent relays; protection logic; protection sensitivity; relay backup protection; relay interconnection; relay setting; upstream breaker; zone interlocking; Delay effects; Digital relays; Fault currents; Impedance; Industrial plants; Power system faults; Power system relaying; Protection; Protective relaying; Senior members;
fLanguage
English
Publisher
ieee
Conference_Titel
Industrial and Commercial Power Systems Technical Conference, 2001. Conference Record. Papers Presented at the 2001 Annual Meeting. 2001 IEEE
Conference_Location
New Orleans, LA
Print_ISBN
0-7803-7055-4
Type
conf
DOI
10.1109/ICPS.2001.966522
Filename
966522
Link To Document