• DocumentCode
    1912097
  • Title

    Performance testing low voltage ground fault protection

  • Author

    Coyle, Timothy

  • Author_Institution
    Sebesta Blomberg & Associates, Roseville, MN, USA
  • fYear
    2001
  • fDate
    37012
  • Firstpage
    147
  • Lastpage
    156
  • Abstract
    The National Electrical Code requires ground fault protection (GPF) of equipment by devices intended to detect and interrupt low-current arcing phase-to-ground faults on many solidly-grounded low voltage systems having current ratings of 1000 A or greater. This code also dictates field performance testing of ground fault protection, but does not prescribe specific techniques to be used. This paper reviews the types of ground fault protection equipment and systems in use today, ranging from simple bolted-pressure switch and relay combinations to complex multiple-source systems and zone-selective-interlocked systems. Conditions that can cause misoperation of ground fault protection are reviewed, including a summary of problems identified during field testing of actual projects. Available testing techniques are reviewed and primary current injection is recommended as the most reliable means of field verification for most ground fault protection systems. Required test equipment setup for each system configuration is described, and cautions to be observed during this type of testing are presented. This paper benefits engineers and technicians responsible for acceptance testing of electrical equipment
  • Keywords
    circuit breakers; earthing; power distribution faults; power distribution protection; relay protection; switchgear testing; National Electrical Code; bolted-pressure switch; field performance testing; ground fault protection; ground fault protection commissioning; ground fault protection misoperation; low-current arcing phase-to-ground faults detection; low-current arcing phase-to-ground faults interruption; multiple-source systems; performance testing; primary current injection; protective relays; relay combinations; testing; zone-selective-interlocked systems; Electrical fault detection; Fault diagnosis; Low voltage; Phase detection; Protection; Protective relaying; Reliability engineering; Switches; System testing; Test equipment;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial and Commercial Power Systems Technical Conference, 2001. Conference Record. Papers Presented at the 2001 Annual Meeting. 2001 IEEE
  • Conference_Location
    New Orleans, LA
  • Print_ISBN
    0-7803-7055-4
  • Type

    conf

  • DOI
    10.1109/ICPS.2001.966525
  • Filename
    966525