Use of ducting to improve inlet air conditions for side-to-side airflow switches in data centers
Author :
Fleming, Jim ; Narasimhan, Susheela
Author_Institution :
Panduit, Burr Ridge, IL, USA
Abstract :
Switches deployed in data centers often utilize side-to-side airflow cooling. This airflow pattern can cause heated exhaust air to flow to the inlet of adjacent equipment in open rack installations or re-circulate to the switch inlet in cabinet applications. Through the use of CFD and testing, ducting solutions have been developed that improve inlet air conditions for both open rack and cabinet applications. Additionally, the ducting solutions make the side-to-side airflow switches compatible with hot aisle/cold aisle layouts as well as air containment solutions.
Keywords :
air conditioning; computational fluid dynamics; computer centres; cooling; installation; CFD; adjacent equipment; air containment solutions; data centers; ducting solutions; exhaust air; inlet air conditions; open rack installations; side-to-side airflow cooling; side-to-side airflow switches; Atmospheric modeling; Computational fluid dynamics; Ducts; Fans; Heating; Particle separators; Testing; Data center; Ducts; Side-to-side airflow; Switches;