DocumentCode :
1912553
Title :
Use of ducting to improve inlet air conditions for side-to-side airflow switches in data centers
Author :
Fleming, Jim ; Narasimhan, Susheela
Author_Institution :
Panduit, Burr Ridge, IL, USA
fYear :
2012
fDate :
18-22 March 2012
Firstpage :
293
Lastpage :
301
Abstract :
Switches deployed in data centers often utilize side-to-side airflow cooling. This airflow pattern can cause heated exhaust air to flow to the inlet of adjacent equipment in open rack installations or re-circulate to the switch inlet in cabinet applications. Through the use of CFD and testing, ducting solutions have been developed that improve inlet air conditions for both open rack and cabinet applications. Additionally, the ducting solutions make the side-to-side airflow switches compatible with hot aisle/cold aisle layouts as well as air containment solutions.
Keywords :
air conditioning; computational fluid dynamics; computer centres; cooling; installation; CFD; adjacent equipment; air containment solutions; data centers; ducting solutions; exhaust air; inlet air conditions; open rack installations; side-to-side airflow cooling; side-to-side airflow switches; Atmospheric modeling; Computational fluid dynamics; Ducts; Fans; Heating; Particle separators; Testing; Data center; Ducts; Side-to-side airflow; Switches;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), 2012 28th Annual IEEE
Conference_Location :
San Jose, CA
ISSN :
1065-2221
Print_ISBN :
978-1-4673-1110-6
Electronic_ISBN :
1065-2221
Type :
conf
DOI :
10.1109/STHERM.2012.6188863
Filename :
6188863
Link To Document :
بازگشت