• DocumentCode
    1918016
  • Title

    Effect of three-winding transformer models on the analysis and protection of mine power systems

  • Author

    Oommen, Mathew P. ; Kohler, Jeffery L.

  • Author_Institution
    Dept. of Miner. Eng., Pennsylvania State Univ., University Park, PA, USA
  • fYear
    1993
  • fDate
    2-8 Oct 1993
  • Firstpage
    2429
  • Abstract
    The impact of accurate, three-winding transformer models in the analysis of mine power systems is examined. Though the disparity in voltage regulation is minimal, the enhanced representation of three-winding transformers seriously affects the results of both steady-state and first-cycle fault analysis. Fault current magnitudes could be underestimated by as much as 60% at strategic locations in the mine power system. This directly affects the choice and sizing of protective and coordination devices used in mine power systems. The effect of winding temperature is also important, but the values do not vary too much from values computed for correctly represented, four-bus, three winding transformer models
  • Keywords
    fault currents; mining; power systems; power transformers; thermal analysis; transformer windings; coordination devices; fault currents; first-cycle fault analysis; mine power systems; overcurrent protection; representation; steady state fault analysis; three-winding transformer models; voltage regulation; winding temperature; Circuit analysis computing; Equations; Impedance; Magnetic circuits; Performance analysis; Power system analysis computing; Power system modeling; Power system protection; Power system transients; Transient analysis;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industry Applications Society Annual Meeting, 1993., Conference Record of the 1993 IEEE
  • Conference_Location
    Toronto, Ont.
  • Print_ISBN
    0-7803-1462-X
  • Type

    conf

  • DOI
    10.1109/IAS.1993.299221
  • Filename
    299221