DocumentCode
1922832
Title
An integrated autonomous protection system against voltage instability based on Load Tap Changers
Author
Vournas, C. ; Lambrou, C. ; Glavic, M. ; Van Cutsem, T.
Author_Institution
Sch. of Electr. & Comput. Eng., Nat. Tech. Univ. of Athens, Athens, Greece
fYear
2010
fDate
1-6 Aug. 2010
Firstpage
1
Lastpage
14
Abstract
In this paper we propose a local, completely autonomous protection system against voltage instability that can be readily integrated in the controller of each bulk power delivery LTC transformer. The protection system will identify an imminent voltage instability and will subsequently apply the necessary corrective measures to restore stable operation by properly adjusting the distribution voltage setpoint of the LTC. Application of this system on a 52-bus test system showed excellent performance for two unstable cases. For reasons of comparison, the indirect load curtailment proposed in a severe instability case is compared with direct load shedding schemes based on the local detection of instability, as well as on a global detection of instability assuming wide area measurements.
Keywords
load shedding; on load tap changers; power distribution protection; LTC transformer; direct load shedding schemes; distribution voltage setpoint; integrated autonomous protection system; on load tap changers; voltage instability; Delay effects; Monitoring; Power system dynamics; Power system stability; Stability analysis; Voltage control; Voltage measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Bulk Power System Dynamics and Control (iREP) - VIII (iREP), 2010 iREP Symposium
Conference_Location
Rio de Janeiro
Print_ISBN
978-1-4244-7466-0
Electronic_ISBN
978-1-4244-7465-3
Type
conf
DOI
10.1109/IREP.2010.5563286
Filename
5563286
Link To Document