• DocumentCode
    1937386
  • Title

    Comparison on unbalanced-load handling capability of two power electronic transformer topologies

  • Author

    Xinyu Wang ; Shaodi Ouyang ; Jinjun Liu ; Taotao Xu ; Xiaojian Wang ; Linyuan Zhou

  • Author_Institution
    State Key Lab. of Electr. Insulation & Power Equip., Xi´an Jiaotong Univ., Xi´an, China
  • fYear
    2013
  • fDate
    15-19 Sept. 2013
  • Firstpage
    5266
  • Lastpage
    5272
  • Abstract
    Power electronic transformer (PET) has many merits as compared with traditional power transformer. In this paper, the unbalanced-load handling capability of two H-bridge based modular PET topologies, the separate-phase-connection (SPC) one and the cross-phase-connection (CPC) one, are analyzed. The two topologies consist of input stage, isolation stage and output stage. The related operating ranges for the two topologies are obtained if the system is confirmed. It finds that the former can deal with full-range unbalanced load if device current stress of the input-stage is increased to 115% while the latter is suitable for dealing with partial unbalanced-load conditions. From practical point of view, the former is more suitable for practical applications. Simulation results verify the analysis.
  • Keywords
    power transformers; CPC; H-bridge based modular PET topology; SPC; cross-phase-connection; partial unbalanced-load conditions; power electronic transformer topology; separate-phase-connection; unbalanced-load handling capability; Inductors; Positron emission tomography; Power transformer insulation; Stress; Topology; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Energy Conversion Congress and Exposition (ECCE), 2013 IEEE
  • Conference_Location
    Denver, CO
  • Type

    conf

  • DOI
    10.1109/ECCE.2013.6647414
  • Filename