DocumentCode :
1942015
Title :
Preliminary investigation into the use of the cross Wigner-Ville distribution to detect high impedance earth faults in power systems
Author :
Palmer, E. ; Ledwich, G. ; Deriche, M.
Author_Institution :
Sch. of Electr. & Electron. Syst. Eng., Queensland Univ., Brisbane, Qld., Australia
Volume :
1
fYear :
2003
fDate :
1-4 July 2003
Firstpage :
597
Abstract :
This paper presents the results of a preliminary investigation into the viability of using the cross Wigner-Ville distribution (XWVD) in the detection of high impedance earth faults in power systems. High impedance earth faults are characterised an extremely low current with a time varying spectral characteristic superimposed on the mains current. It is shown that the XWVD provides a good identification of the extremely small high impedance arc fault current with signal to noise ratios as low as -10dB.
Keywords :
Wigner distribution; electric impedance measurement; fault currents; fault diagnosis; power system faults; XWVD; cross Wigner-Ville distribution; high impedance earth fault detection; power systems; time varying spectral characteristic; Australia; Conductors; Earth; Electrical fault detection; Fault currents; Fault detection; Frequency; Impedance; Power system faults; Power system protection;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Signal Processing and Its Applications, 2003. Proceedings. Seventh International Symposium on
Print_ISBN :
0-7803-7946-2
Type :
conf
DOI :
10.1109/ISSPA.2003.1224774
Filename :
1224774
Link To Document :
بازگشت