Abstract :
In this paper, we propose an application of a developed fault location platform to the Taiwan transmission grid using transmitted synchronized IED (Intelligent Electronic Device) data as inputs to the platform via Ethernet. The proposed fault location platform can also be applied to utilities with IEDs around the world. IED measurements are synchronized with embedded phasor measurement unit (PMU) function in IEDs or with unsynchronized measurements correction method in the platform. The functions of the fault location platform consist of COMTRADE file converter, faulted waveform display function, digital filter, two-terminal and three-terminal transmission line fault location algorithms, unsynchronized measurements correction method, and graphical display of fault location. Due to the high accuracy and fast analysis features of the platform, utilities can reduce large amount of manpower cost and power interruption cost during a fault searching period. Field event results of the platform over the Taiwan power system are provided to demonstrate the claimed features.
Keywords :
intranets; local area networks; phasor measurement; power engineering computing; power grids; power transmission faults; COMTRADE file converter; Ethernet; IED measurements; Taiwan power system; Taiwan transmission grid; digital filter; embedded phasor measurement unit function; embedded-PMU function; fault searching period; faulted waveform display function; graphical display; intranet-based transmission grid fault location platform; power interruption cost; three-terminal transmission line fault location algorithms; transmitted synchronized IED data; transmitted synchronized intelligent electronic device data; two-terminal transmission line fault location algorithms; unsynchronized measurement correction method; Compounds; Fault location; Indexes; Phasor measurement units; Power transmission lines; Synchronization; Transmission line measurements; Intelligent Electronic Device (IED) phasor measurement unit; Transmission Line Fault Location Platform;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Innovative Smart Grid Technologies (ISGT), 2013 IEEE PES
Conference_Location :
Washington, DC
Print_ISBN :
978-1-4673-4894-2
Electronic_ISBN :
978-1-4673-4895-9
Type :
conf
DOI :
10.1109/ISGT.2013.6497796
Filename :
6497796
Link To Document :
بازگشت