  • Abstract
    The Electromagnetic Transients Program (EMTP) after minor adaptation is utilized to simulate the grounded fault of a cable in a steel-pipe. The zero sequence impedance became nonlinear during the fault period, because the zero sequence current in a steel-pipe induced a magnetic saturation effect. Consequently, the zone protection of a cable in a steel-pipe has a serious error if a traditional distance relay is used. To correct this possible malfunction a novel idea using the proposed digital relay is presented. The physical zero sequence impedance will dynamically be modified according to the zero sequence current in case of a grounded fault. With such real cable data, an accurate fault location of cable in a steel-pipe is accordingly estimated
  • Keywords
    electric conduits; electric impedance; fault location; power cables; relay protection; underground cables; EMTP; Electromagnetic Transients Program; cable; digital relay; fault location identification; grounded fault simulation; induced magnetic saturation effect; nonlinear zero sequence impedance; steel-pipe; zero sequence current; Circuit faults; Communication cables; Digital relays; EMTP; Fault detection; Fault diagnosis; Fault location; Impedance; Power cables; Protective relaying;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Energy Management and Power Delivery, 1998. Proceedings of EMPD '98. 1998 International Conference on
  • Print_ISBN
    0-7803-4495-2
  • Type

    conf

  • DOI
    10.1109/EMPD.1998.705550
  • Filename
    705550