DocumentCode
1954962
Title
Optimization of neutral grounding reactor parameters-an analysis for a double circuit EHV line
Author
Nayak, R.N. ; Sehgal, Y.K. ; Sen, Subir ; Gupta, Manju
Author_Institution
Power Grid Corp. of India Ltd., Gurgaon
fYear
0
fDate
0-0 0
Abstract
In order to maintain power transmission reliability, application of single-phase switching (SPS) and auto-reclosing on EHV line is a common practice. However, in some cases, it is necessary to apply special means like neutral grounding reactor (NGR) to improve the conditions for secondary arc extinction for successful auto-reclosing. This paper presents importance of various parameters in optimization of NGR in a double circuit (D/c) EHV line. In case of SPS on D/c line, the secondary arc is maintained not only by the inter-phase coupling of the faulted circuit but also by the mutual coupling of the other healthy circuit. An empirical formula for NGR value of a double circuit line along with the methodology for its optimization is presented. Magnitude of secondary arc current also depends on the line length, power flow, source strength etc. Sensitivity of various parameters on secondary arc current has been demonstrated through EMTP study
Keywords
EMTP; arcs (electric); load flow; optimisation; power system analysis computing; power transmission faults; power transmission lines; power transmission reliability; reactors (electric); EMTP; autoreclosure; double circuit EHV line; inter phase coupling; mutual coupling; neutral grounding reactor; optimization; power flow; power transmission reliability; recovery voltage; secondary arc extinction; single-phase switching; Circuit faults; Coupling circuits; EMTP; Grounding; Inductors; Load flow; Maintenance; Mutual coupling; Optimization methods; Power transmission;
fLanguage
English
Publisher
ieee
Conference_Titel
Power India Conference, 2006 IEEE
Conference_Location
New Delhi
Print_ISBN
0-7803-9525-5
Type
conf
DOI
10.1109/POWERI.2006.1632567
Filename
1632567
Link To Document