Abstract :
The objective of this paper is to apply Principal Component Analysis to evaluate the aging state of the insulation system of the generators of Salto Grande identifying the mostly aged units. This hydropower plant has 14 generators of 135 MW each, with an average age of 32 years. From the analysis it was concluded that there is no evidence of critical units, which require rapid intervention. But there is an aging process, which is not equal on all generators, as there are generators showing a more advanced aging stage. This is key information to define a work plan for maintenance, or to recommend detailed inspections by specialists, or define an upgrade plan.
Keywords :
ageing; hydroelectric generators; hydroelectric power stations; insulation; principal component analysis; synchronous generators; Salto Grande Hydroelectric; aging process; aging state; hydropower plant; insulation system; power 135 MW; power generators; principal component analysis; Aging; Covariance matrices; Generators; Insulation; Principal component analysis; Rotors; Silicon; Hidropower plant; Insulation system; Principal Component Analysis; Synchronous generators;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Biennial Congress of Argentina (ARGENCON), 2014 IEEE
Conference_Location :
Bariloche
Print_ISBN :
978-1-4799-4270-1
Type :
conf
DOI :
10.1109/ARGENCON.2014.6868526
Filename :
6868526
Link To Document :
بازگشت