Development of a fault current limiter for 22.9 kV distribution power line
Author :
Min Jee Kim ; Wonjoon Choe ; Seung-Hyun Bang ; Hae Yong Park ; Gyeong-Ho Lee ; Jungwook Sim ; Kil-Young Ahn ; Jong Ho Lee ; Young-Keun Kim ; Jung Kwon Yang
Author_Institution :
Electro-Technol. R&D Center, LSIS Co., Ltd., Cheongju, South Korea
Abstract :
A 25.8 kV/600 A/12.5 kA fault current limiter (FCL) for 22.9 kV distribution power line has successfully designed, manufactured, and field tested at KEPCO Power Testing Center for the protection coordination. FCL is composed of fast fault detector (FFD) developed as a key component, mechanical fast switch (FS), and current limiting resistor (CLR). The FFD plays a role in sensing a fault current, which is recognized when it passes over the certain fault current level. The FFD has 5 fault current levels between 0.9 kA and 3 kA, and the fault current levels can be selected according to the electrical power systems. This function makes FCL more simple, economical, manageable and useful in various electrical power systems in comparison with a superconductor of a superconducting FCL. The FS has a function of a current commutation from main circuit to the CLR when fault occurs by using of a vacuum interrupter (VI). The CLR´s role is to reduce the fault current by its impedance, which is decided based on the power system analysis of an application site. The whole process is perfectly completed within 1 cycle after the fault occurs. Recently, short circuit test, impedance test, and the electrical insulation test are passed. And also the field test is performed on the 1.5 kA and 5.0 kA faults, which are made by connecting the Artificial Fault Generator (AFG) to the distribution line in test grid at KEPCO Power Testing Center. Various demonstration tests of the FCL have proved that the current limiting performance is satisfactory and the protection coordination with conventional relays is realized.
Keywords :
distribution networks; fault current limiters; vacuum interrupters; artificial fault generator; current 0.9 kA to 3 kA; current 12.5 kA; current 600 A; current commutation; current limiting resistor; distribution power line; fast fault detector; fault current limiter; mechanical fast switch; protection coordination; vacuum interrupter; voltage 22.9 kV; voltage 25.8 kV; Hafnium; Insulation; Radio access networks; Reliability; Switches; Vacuum technology;
Conference_Titel :
Electric Power Equipment - Switching Technology (ICEPE-ST), 2013 2nd International Conference on
Conference_Location :
Matsue
DOI :
10.1109/ICEPE-ST.2013.6804378