Abstract :
When the current reference of a shunt active power filter (SAPF) changes quicker than the output current can change, the output of the APF cannot precisely track the current reference. Undesired harmonics will be generated by the APF due to the controller saturation. Based on detailed analysis of the reason and consequences of the controller saturation problem, this paper proposes an adaptive saturation scheme to suppress the effect of saturation by using the feedback of the current error signal. The proposed scheme can adaptively adjust the capacity of the APF according to different load conditions. The adjusted reference is still in phase with the original calculated harmonics and contains no extra undesired harmonics. Also, this algorithm has no risk of affecting the reference when there is no saturation. Simulation results show that the proposed scheme can operate effectively and the effect of saturation is greatly reduced
Keywords :
active filters; adaptive control; power filters; power system harmonics; adaptive saturation scheme; controller saturation problem; error signal; feedback; load condition; output current; shunt active power filter; Active filters; Delay; Error correction; Inverters; Power engineering and energy; Power engineering computing; Power harmonic filters; Power system harmonics; Reactive power; Shunt (electrical);
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Control Applications, 2005. CCA 2005. Proceedings of 2005 IEEE Conference on
Conference_Location :
Toronto, Ont.
Print_ISBN :
0-7803-9354-6
Type :
conf
DOI :
10.1109/CCA.2005.1507373
Filename :
1507373
Link To Document :
بازگشت