DocumentCode :
1984497
Title :
A new method of detecting current transducer saturation based on wavelet transform
Author :
Guicun, Li ; Wanshun, Liu ; Qingquan, Jia ; Lin, Teng ; Fengmei, Cao ; Ying, Li
Author_Institution :
Sifang Inst. North China Electr. Power Univ., Beijing, China
Volume :
1
fYear :
2001
fDate :
15-19 July 2001
Firstpage :
617
Abstract :
Bus bar differential protection using instantaneous current values is easily influenced by current transducer (CT) saturation, causing maloperation. A method of analyzing the voltage of busbars using the wavelet transform is presented in this paper to detect fault points accurately. One can distinguish whether the CT is saturated based on the time difference between the time of the fault and the time of differential current.
Keywords :
busbars; electric current measurement; power system measurement; transducers; wavelet transforms; busbar differential protection; current transducer saturation detection; fault point detection; power system; wavelet transform; Circuit faults; Fault currents; Fault detection; Fourier transforms; Power system protection; Signal analysis; Signal processing; Transducers; Wavelet analysis; Wavelet transforms;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering Society Summer Meeting, 2001
Conference_Location :
Vancouver, BC, Canada
Print_ISBN :
0-7803-7173-9
Type :
conf
DOI :
10.1109/PESS.2001.970109
Filename :
970109
Link To Document :
بازگشت