  • Title

    Experimental designs for tracking the influent operating parameters on insulation reliability

  • Author

    Khelil, Y. ; Maussion, P. ; Lebey, T.

  • Author_Institution
    LAPLACE, Univ. de Toulouse; INPT, Toulouse, France
  • fYear
    2009
  • fDate
    Aug. 31 20096-Sept. 3 2009
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    In order to underline the influence of combined operating constraints in insulation reliability, some experiments were carried out according to the experimental design methodology. Kapton films and coated wires were subjected to an accelerated aging under combined stresses (VRMS, frequency, DC voltage, and temperature). Samples life time measurements allowed us classify the parameters with respect to their influence order. Frequency shift from 1 to 10 kHz is more hazardous than a voltage shift from 0.7 to 1.2 kV or a temperature shift from 150 to 200degC. Adding a DC voltage as 200V increased the sample life time. Thanks to experimental design, different mathematical models of sample life time have been established.
  • Keywords
    ageing; insulating materials; reliability; wires (electric); DC voltage; Kapton films; accelerated aging; coated wires; combined stresses; influent operating parameter tracking; insulation reliability; mathematical models; voltage 200 V; Accelerated aging; Design for experiments; Frequency; Insulation life; Mathematical model; Stress; Temperature; Time measurement; Voltage; Wires; Dielectric breakdown; Dielectric films; Insulation life; Insulation testing; Life estimation; Modeling;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Diagnostics for Electric Machines, Power Electronics and Drives, 2009. SDEMPED 2009. IEEE International Symposium on
  • Conference_Location
    Cargese
  • Print_ISBN
    978-1-4244-3441-1
  • Type

    conf

  • DOI
    10.1109/DEMPED.2009.5292779
  • Filename
    5292779