DocumentCode
1985984
Title
SVC for resonance control in NamPower electrical power system
Author
Halonen, M. ; Rudin, S. ; Thorvaldsson, B. ; Kleyenstuber, Udo ; Boshoff, Septimus ; van der Merwe, C.
Author_Institution
ABB Power Syst., Vasteras, Sweden
Volume
2
fYear
2001
fDate
15-19 July 2001
Firstpage
860
Abstract
The extension of the Namibian transmission system results in a near 50 Hz resonance. To control the resonance a SVC was installed at Auas 400 kV substation. A new control principle for controlling the resonance was developed and tested. The paper presents the background to the resonance problem, the Auas SVC configuration, the resonance controller and finally the conclusions from extensive test results, both from simulator and site tests.
Keywords
power system control; resonance; static VAr compensators; substations; voltage control; 400 kV; 50 Hz; Auas substation; Namibian transmission system extension; SVC; control design; d/q-transformation; reactive power; real time digital simulator; resonance control; resonance controller; static VAr compensator; sustained transient overvoltage; Africa; Control systems; Power generation; Power system control; Power systems; Resonance; Static VAr compensators; Substations; Testing; Voltage control;