DocumentCode :
1986922
Title :
A new method of fault location on transmission lines
Author :
Yin, Xing ; Wang, Fangzong
Author_Institution :
Coll. of Electr. Eng. & New Energy, China Three Gorges Univ., Yichang, China
fYear :
2011
fDate :
16-18 Sept. 2011
Firstpage :
475
Lastpage :
479
Abstract :
This paper presents a new technique of accurate fault location based on an improved joint diagonalization algorithm - Three Iterations Algorithm(TIA). It employs the fault generated high-frequency transients, which contain abundant fault information. The FFT algorithm and TIA are combined to analyze the selected mode component of the fault generated high frequency transients to accurately found the difference of the adjacent natural frequencies and realize the fault location. A typical 500kV system in MATLAB is used to verify the performance. The simulation results show that the proposed method can improve the accuracy of fault location, whereas require less sampling points and less computation.
Keywords :
fast Fourier transforms; fault location; iterative methods; power transmission faults; power transmission lines; FFT algorithm; Matlab; TIA; adjacent natural frequencies; fault generated high-frequency transients; fault location; improved joint diagonalization algorithm; three-iteration algorithm; transmission lines; Circuit faults; Fault location; Joints; Power transmission lines; Signal processing algorithms; Transient analysis; FFT algorithm; Three Iterations Algorithm; fault location; natural frequency; transmission line;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical and Control Engineering (ICECE), 2011 International Conference on
Conference_Location :
Yichang
Print_ISBN :
978-1-4244-8162-0
Type :
conf
DOI :
10.1109/ICECENG.2011.6057688
Filename :
6057688