  • Abstract
    This paper presents a new proposal for the detection of arcing faults (AF) and evaluates the detection rate and the security level of the proposed method. This method is based on an analysis of three-phase unbalanced current, feeder 3I/sub 0/, using decomposition of the signal by means of wavelet transform techniques. Combining both temporal and frequency localizing properties, criteria are set in order to detect electric arc existence related to high impedance faults. The method has been tested with signals from staged fault records, normal condition records and substation event records. The test results show that the proposal is a satisfactory fault detection method.
  • Keywords
    arcs (electric); fault diagnosis; power distribution faults; wavelet transforms; detection rate; distribution network arcing fault detection method; frequency localizing properties; high impedance faults; security level; temporal localizing properties; three-phase unbalance current; wavelet packet analysis; Electrical fault detection; Fault detection; Frequency; Impedance; Proposals; Security; Signal analysis; Testing; Wavelet analysis; Wavelet transforms;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society Summer Meeting, 2001
  • Conference_Location
    Vancouver, BC, Canada
  • Print_ISBN
    0-7803-7173-9
  • Type

    conf

  • DOI
    10.1109/PESS.2001.970269
  • Filename
    970269