Abstract
A study of low frequency inter-area oscillation which appears during the process of the interconnection of power grids is presented in this paper. The eigenvalue sensitivity with respect to inter-area transfer admittance is suggested to analyze the extent of the power gridspsila tightness, and to manifest the influence of the power grid connection mode on the power system stability, which shows that as the deterioration of the power gridspsila interconnection tightness, the damping ratio of the low frequency inter-area oscillation gets smaller and the frequency of the inter-area oscillation gets lower. An example of Central China Grid is studied to verify the validity of the theoretical analysis, and a different power system structure is suggested to enhance the damping of the low frequency oscillation.
Keywords
eigenvalues and eigenfunctions; power grids; power system interconnection; power system stability; Central China Grid; eigenvalue sensitivity; power grid interconnection; power system stability; power system structure; Admittance; Damping; Eigenvalues and eigenfunctions; Frequency; Power grids; Power system analysis computing; Power system interconnection; Power system stability; Signal analysis; Stability analysis; Eigenvalue; damping; inter-area oscillation; low frequency; power grid;
fLanguage
English
Publisher
ieee
Conference_Titel
System of Systems Engineering, 2008. SoSE '08. IEEE International Conference on
Conference_Location
Singapore
Print_ISBN
978-1-4244-2172-5
Electronic_ISBN
978-1-4244-2173-2
Type
conf
DOI
10.1109/SYSOSE.2008.4724176
Filename
4724176
Link To Document